Technical Data:

 

CommunicationsPROFINET IO
Device-specificSupported profiles: PROFIsafe V2, PROFIenergy V1.0; ID code: Vendor ID: 0x011D; Device ID: 0x02EE; Module ID: 0x01000177 (firmware version 01, 02), 0x02000177 (from firmware version 03)
PROFINET IO featuresIntegrierter 2-Port-Switch; Autonegotiation; Auto-MDIX; isochrone Echtzeitkommunikation; Sendetakt: 1 ms (RT); 1, 2, 4 ms (IRT); Gerätetausch ohne Programmiergerät
Transmission rate10/100 Mbit/s (10 Mbit/s (ETHERNET protocols), 100 Mbit/s full duplex (PROFINET IO))
Bus segment length (max.)100 m
Transmission medium (communication/fieldbus)Twisted pair S-UTP; 100 Ω; Cat. 5
Number of modules per node (max.)250
Number of modules without a bus extension (max.)64
Input and output process image (fieldbus) max.512 bytes/512 bytes
Supply voltage (system)24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection)
Current consumption (5 V system supply)450mA
Total current (system supply)1,700mA
Supply voltage (field)24 VDC (-25 … +30 %); via power jumper contacts
Input current (typ.) at nominal load (24 V)500mA
Power supply efficiency (typ.) at nominal load (24 V)90%
Isolation500 V system/field
Number of outgoing power jumper contacts3
Current carrying capacity (power jumper contacts)10A

Fieldbus Coupler PROFINET IO; 3rd Generation; Advanced