Technical Data:

 

CommunicationsModbus RTU
Number of fieldbus nodes on master (max.)247
Number of I/O points6,000
Transmission rate150 Bd … 115.2 kBd
Bus segment length (max.)1200 m
Transmission medium (communication/fieldbus)Shielded Cu cable 2 (4) x 0.25 mm²
Number of modules per node (max.)64
Number of modules without a bus extension (max.)64
Input and output process image (fieldbus) max.512 bytes/512 bytes
Supply voltage (system)24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection)
Current consumption (5 V system supply)350mA
Total current (system supply)1,650mA
Supply voltage (field)24 VDC (-25 … +30 %); via power jumper contacts
Input current (typ.) at nominal load (24 V)500mA
Power supply efficiency (typ.) at nominal load (24 V)87%
Isolation500 V system/field
Number of outgoing power jumper contacts3
Current carrying capacity (power jumper contacts)10A

Fieldbus Coupler MODBUS; RS-232; 115,2 kBd