Technical Data:

 

CommunicationsINTERBUS
Number of fieldbus nodes on master (max.)256
Number of I/O points4,096
Transmission rate500 kBd
Bus segment length (max.)400 m
Transmission medium (communication/fieldbus)Certified Cu cable
Transmission time1.43 ms (10 couplers; each 32 digital I/O)
Number of modules per node (max.)64
Number of modules without a bus extension (max.)64
Input and output process image (fieldbus) max.64 bytes/64 bytes
Supply voltage (system)24 VDC (-15 … +20 %); via pluggable connector (CAGE CLAMP® connection)
Current consumption (5 V system supply)300mA
Total current (system supply)1,700mA
Supply voltage (field)24 VDC (-15 … +20 %); via power jumper contacts
Input current (typ.) at nominal load (24 V)500mA
Power supply efficiency (typ.) at nominal load (24 V)87%
Isolation500 V system/field
Number of outgoing power jumper contacts3
Current carrying capacity (power jumper contacts)10A
CertificationINTERBUS CLUB
StandardEN 50254