Technical Data:

 

Number of analog inputs4
Total number of channels (module)4
Signal typeResistance measurement
Potentiometer positions
Signal type (configurable)yes
Sensor connection4 x (2-wire, 3-wire, 4-wire)
Data width4 x 16-bit data; 4 x 8-bit control/status (optional)
Resolution (over entire range)0.1 °C (over the entire range); 0.01 °C (–50 … 150 °C; Pt1000, Ni1000)
Conversion time (typ.)100ms
Conversion timePer channel: ≤ 100 ms (2-/4-wire connection), ≤ 200 ms (3-wire connection)
Measurement error (25 °C)≤ ±0.6 K (Pt100, Pt200, Pt500, Ni100, Ni120); ≤ ±0.2 K (Pt1000, Ni1000);  ±0.3 … 0.7 Ω for resistance measurement
Measuring current (typ.)≤ 350 µA
Response time (max.)3s
Sensor typesPt100; Configurable: Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000 (TK6180 + TK5000), Potentiometer: 10R … 1k2, 10R … 5k0
Temperature range−200 … +850 °C (Pt100, Pt200, Pt500, Pt1000), −60 … +250 °C (Ni100, Ni1000), −80 … +260 °C (Ni120)
Configuration optionsWAGO-I/O-CHECK
CODESYS Library
e!COCKPIT
Supply voltage (system)5 VDC; via data contacts
Current consumption (5 V system supply)85mA
Supply voltage (field)24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission (field side supply voltage only) via spring contact)
Isolation500 V system/field
IndicatorsLED (1-4) green: Status R1 … R4; LED (5-8) red: Error R1 … R4
Number of incoming power jumper contacts2
Number of outgoing power jumper contacts2