top of page
logo.jpg

Technical Data:

 

Number of analog inputs4
Total number of channels (module)4
Signal typeResistance measurement
Signal type (configurable)yes
Sensor connection4 x (2-wire)
Data width4 x 16-bit data; 4 x 8-bit control/status (optional)
Resolution (over entire range)0.1 °C
Measurement error (25 °C)≤ 0.5 K in temperature range: −30 … +150 °C
Temperature coefficient≤ 20 ppm/K
Measuring current (typ.)≤ 350 µA
Measurement repetition rate (standard)1.1s
Measurement repetition rate (2-channel/2-conductor)0.63s
Response time (max.)4s
Sensor typesPt1000; Configurable: Ni1000, KTY 81
Temperature range−30 … +150 °C
Configuration optionsWAGO-I/O-CHECK
CODESYS Library
e!COCKPIT
Supply voltage (system)5 VDC; via data contacts
Current consumption (5 V system supply)50mA
Supply voltage (field)24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission (field side supply voltage only) via spring contact)
Isolation500 V system/field
IndicatorsLED (A, B, E, F) green: Function AI 1 … AI 4; LED (C, D, G, H) red: Error AI 1 … AI 4
Number of incoming power jumper contacts2
Number of outgoing power jumper contacts2

4-channel analog input; For Pt1000/RTD resistance sensors; Adjustable

    bottom of page